Results of Lead Monitoring in Drinking Water at VŠE Dormitories – Well Below Applicable Health Limits
In accordance with current legislative requirements, indicative monitoring of lead concentrations in drinking water was carried out in 2026 in all dormitories managed by FMD/SÚZ VŠE.
Water samples were collected from selected accommodation areas and analyzed by an accredited laboratory.
The results confirmed that lead concentrations in all monitored buildings were well below the applicable health limits.
Most samples showed concentrations below the detection limit of the analytical method used (< 3 µg/L). The highest measured value was 3.3 µg/L, which remains significantly below both the current limit of 10 µg/L and the future limit of 5 µg/L.
Based on the monitoring results, the risk of lead contamination in drinking water was assessed as low in all residence hall buildings. No corrective measures are therefore required.
Detailed results can be found in the attached report CZ.
FMD/SÚZ VŠE